INSTALLATION INSTRUCTION Air or Water Cooled Chillers 1. When the chiller is received, check for any shipping damage. If any is found, a freight cl
proper rotation. The water pump switch must be on in order to check rotation of fan motor. The refrigeration system will not run unless the water pump
SPECIAL INSTRUCTIONS WATER PUMP The water pump is controlled by the manual switch for off and on operations. The motor on this pump has a built-in o
CHILLED WATER CIRCUIT The chilled water is pumped from the chiller's water tank to the discharge outlet of the chiller. Then from the discharge
REFRIGERATION SYSTEM The refrigeration system is a medium temperature system with a range from 350 F to 700 F. This is the most efficient range. If
FAN MOTORS AIR COOLED SPECIFICATIONS: H.P. 1 – 2 each VOLTAGE - 460/200/230 PHASE 3 HZ-50-60 RPM 1725 OVERLOAD - Automatic, Internal FRAME -
MAINTENANCE INFORMATION 1. 2. There are no lubrication points on the chiller. All motors have permanent lubrication in the bearings. The water that
TROUBLE SHOOTING - PART I SYMPTOM DIAGNOSIS REMEDY Compressor won't run Check Power supply Electrical circuit Check Line load
TROUBLE SHOOTING - PART II REFRIGERATION SYSTEM INTERNAL PRESSURE USING REFRIGERANT R-22 * High Pressure Switch : Manual Reset - Cut out at 425 P.
PARTS LIST 2000AC/WC - 460/3 or 230/3 If this unit has special feature(s) installed, see appendix for part number(s). Part Number Description 460/
E151 Fan Rain Shield 9 9 2 Plumbing P128-S Stainless Steel Water Pump – 5 hp 9 9 1 P145-3S Seal & “O” Ring Kit for Water Pump 9 9 1 P152 C
WATER CHILLER STARTING CHECKLIST PROPER VOLTAGE Check the voltage on the chiller to see that it matches your power supply. CRANK CAS
CONT. WATER CHILLER STARTING CHECKLIST ELECTRIC – POWER A good test to make sure power is off to the unit is to turn on the water pump sw
Models:Voltage:Options:230-460Schreiber Engineering12111 Park St. Cerritos, CA(562)-926-3855(562)-926-0969 FaxPhase: 3Type:Air/Water Coole
SETTING SOLID STATE CONTROL This unit has solid-state controls that regulates the temperature of the refrigeration system. After the unit is wired t
CHILLED WATER DISTRIBUTION PIPING The chilled water distribution piping is an important factor in the performance of the water chiller. Proper piping